Cooling Circuit Leakage Protection system KMP-K
Kamstrup
|
Principle
Cooling Circuit Leakage Protection system KMP-K employs values of volume flow from two flow meters,
which are fetched regularly via a digital interface from a Kamstrup
MULTICAL®602, 801, or 6M2 energy meter to
which the flow meters are attached.
Two monitoring functions are employed with the fetched flow data for protecting the installation
from leakagem as the KMP-K closes the cut-off valves when a leak is detected by any monitor.
Component errors reported in the heat meters's INFO code are propagated by the KMP-K as
System Fault alarm.
|
|
Logging
Alarm and Event log
KMP-K maintains a log over the most recent 250 events. Events include power down/up,
alarm and error reports, acknowledgements and autoreset, key input, control input
and sequencer action.
|
Jumper log
KMP-K maintains a log of the 15 most recent changes to the internal jumper setting.
These logs contribute to clarification and documentation of actual events.
|
|
System K6A (K8A) |
Capacity and Pressure Loss |
Dimensions |
Nom. Cap. qp (m³/h) |
ΣΔp@qp |
Equivalent Kv (m³/h) |
(mwc) |
(kPa) |
Flow Meter |
Valve |
Check Valve |
KMP-K6A1,5 |
1,5 |
3,5 |
35 |
2,6 |
G¾B x 110 mm (R½) |
½" x 77 mm |
½" x 48 mm |
KMP-K6A2,5 |
2,5 |
3,1 |
31 |
4,5 |
G1B x 190 mm (R¾) |
¾" x 77 mm |
¾" x 53 mm |
KMP-K6A3,5 |
3,5 |
2,3 |
23 |
7,4 |
G5/4B x 260 mm (R1) |
1" x 90 mm |
1" x 59 mm |
KMP-K6A6 |
6 |
4,6 |
46 |
8,8 |
G5/4B x 260 mm (R1) |
1¼" x 110 mm |
1¼" x 66 mm |
KMP-K6A10 |
10 |
2,4 |
24 |
20 |
G2B x 300 mm (R1½) |
1½" x 120 mm |
1½" x 71 mm |
KMP-K6A10F |
10 |
2,4 |
24 |
20 |
DN40 x 300 mm |
1½" x 120 mm |
1½" x 71 mm |
KMP-K6A15 |
15 |
3,8 |
38 |
24 |
DN50 x 270 mm |
2" x 140 mm |
2" x 80 mm |
KMP-K6A25 |
25 |
2,4 |
24 |
51 |
DN65 x 300 mm |
DN65 x 46 mm |
DN65 x 54 mm |
KMP-K6A40 |
40 |
2,1 |
21 |
88 |
DN80 x 300 mm |
DN80 x 46 mm |
DN80 x 57 mm |
KMP-K6A60 |
60 |
1,3 |
13 |
169 |
DN100 x 360 mm |
DN100 x 52 mm |
DN100 x 64 mm |
KMP-K6A100 |
100 |
3,5 |
35 |
169 |
DN100 x 360 mm |
DN100 x 52 mm |
DN100 x 64 mm |
KMP-K6A150 |
150 |
0,83 |
8,3 |
519 |
DN150 x 500 mm |
DN150 x 56 mm |
DN150 x 76 mm |
KMP-K6A400 |
400 |
1,2 |
12 |
1162 |
DN200 x 500 mm |
DN200 x 60 mm |
DN200 x 95 mm |
KMP-K6A600 |
600 |
1,2 |
12 |
1723 |
DN250 x 600 mm |
DN250 x 68 mm |
DN250 x 108 mm |
KMP-K6A1000 |
1000 |
1,3 |
13 |
2779 |
DN250 x 600 mm |
DN300 x 78 mm |
DN300 x 143 mm |
|
|
KMP-K8I and KMP-K6M
Flow meters and valves are selected for each system individually according to
media type and operating conditions; hence there are no general system tables
for these families.
Variants
Variant -M2 is a complete new delivery.
Variants -M1 and -M0 are used with an existing Kamstrup cooling meter.
Note an existing cooling meter must be mains supplied for use with KMP-K.
|
Delivery KMP-K
Variant (suffix) |
-M2 |
-M1 |
-M0 |
KMP-K control unit |
1 |
1 |
1 |
Cut-off valves |
2 |
2 |
2 |
Check valve |
1 |
1 |
1 |
MULTICAL®calculator |
1 |
0 |
0 |
Flow meters |
2 |
1 |
0 |
Data module (KMP-K6A/K6M) |
1 |
1 |
1 |
|
The DanTaet systems are protected ny patents issued and pending and copyright in