District Heating Leak Protection System KMP-F
Kamstrup

Principle

District Heating Leak Protection system KMP-F employs values of volume flow from two ultrasonic meters, which are fetched regularly via a digital interface from a Kamstrup MULTICAL®601, 602 or 801 heat meter to which the flow meters are attached.

Two monitoring functions are employed with the fetched volume flow data for protecting the installation from leakage, as the KMP-F closes the cut-off valves when a leak is detected by any monitor.

Component errors reported in the heat meter's INFO code are propagated by the KMP-F as System Error Alarms.


 

system diagram KMP-F

Logging


Alarm and Event log
KMP-F maintains a log of the most recent 250 events, such as Power Down, Power Up, Alarm and Error messages, Alarm Acknowledge and Autoreset, External Control Input change, State change and Sequence execution.

 

Jumper Log
KMP-F maintains a log of the 15 most recent changes to the jumper settings.

These logs serve to document events surrounding actual incidents in the installation.

spacer
System Capacity and head loss Dimensions
Nom. Kap.
qp (m³/h)
 ΣΔp@qp Equivalent
Kv (m³/h)
(mwc) (kPa) Flow meter Valve Check Valve
KMP-F0,6 0,6 0,86 8,6 2,1 G¾B x 110 mm (R½) ½" x 77 mm ½" x 48 mm
KMP-F1,5 1,5 3,5 35 2,6 G¾B x 110 mm (R½) ½" x 77 mm ½" x 48 mm
KMP-F2,5 2,5 3,1 31 4,5 G1B x 190 mm (R¾) ¾" x 77 mm ¾" x 53mm
KMP-F3,5 3,5 2,3 23 7,4 G5/4B x 260 mm (R1) 1" x 90 mm 1" x 59 mm
KMP-F6 6 4,6 46 8,8 G5/4B x 260 mm (R1) 1¼" x 110 mm 1¼" x 66 mm
KMP-F10 10 2,4 24 20 G2B x 300 mm (R1½) 1½" x 120 mm 1½" x 71 mm
KMP-F10F 10 2,4 24 20 DN40 x 300 mm 1½" x 120 mm 1½" x 71 mm
KMP-F15 15 3,8 38 24 DN50 x 270 mm 2" x 140 mm 2" x 80 mm
KMP-F25 25 2,4 24 51 DN65 x 300 mm DN65 x 46 mm DN65 x 54 mm
KMP-F40 40 2,1 21 88 DN80 x 300 mm DN80 x 46 mm DN80 x 57 mm
KMP-F60 60 1,3 13 169 DN100 x 360 mm DN100 x 52 mm DN100 x 64 mm
KMP-F100 100 3,5 35 169 DN100 x 360 mm DN100 x 52 mm DN100 x 64 mm
KMP-F150 150 0,83 8,3 519 DN150 x 500 mm DN150 x 56 mm DN150 x 76 mm
spacer

Variants

Variant -M2 is a complete new delivery.
Variants -M1 and -M0 are used with an existing Kamstrup heat meter.
Note that the heat meter must be grid powered for use with KMP-F, and that it must have space available for insertion of a data module.
Systems KMP-FExx employ MULTICAL®801.

Delivery

Variant (suffix) -M2 -M1 -M0
KMP-F Control Unit 1 1 1
Cut-Off Valves 2 2 2
MULTICAL®602 1 0 0
Flow Meters 2 1 0
Data module 1 1 1

page 1